2019/8/1??????view:

  The maximum exhaust pressure shall not be greater than 1.15 bar (absolute pressure). Strictly prevent any blockage in the exhaust pipe. Exhaust filters, accessories and pipes must be estimated according to maximum flow rate. The maximum flow rate is equivalent to the pumping speed of the pump.

  Electrical Connection of ZYD Dual Stage Oil Filter SV Laibao

  1. Wiring warning for motor of vacuum oil filter:

  The input power of the pump must be cut off before the connection of the motor or the replacement of the connection. Electrical wiring must be carried out by qualified electricians in accordance with the application safety regulations.

  The motor connection is connected to the correct supply voltage through the connector in the junction box. See the wiring diagram on the motor or in the wiring box. Correct electrical connection must use appropriate motor protection switch. Set the switch according to the rated value on the motor nameplate.

  2. Cautions for connection of motor of vacuum oil filter:

  After the connection of the motor and whenever the connection is changed, the rotation direction of the motor should be checked. The direction of rotation of the motor should be the same as the direction arrow on the motor cover. When checking, the intake should be opened. If the motor rotates in the wrong direction, oil may be ejected from the intake port. Pressure in the vacuum system may increase.

  Do not use motor fans to check the direction of rotation. Because the motor fan rotates too fast to judge the direction of rotation; when the parking slows down, the fan will keep the original direction of rotation.

  Start the pump briefly, check whether the intake is sucked into the feeling, and then immediately stop the pump. When the pump steers correctly, you should feel sucked into the intake port.

  If you need to change the direction of rotation, cut off the power supply, and exchange two-phase wiring.

  We recommend that the rotation direction be checked with a phase sequence indicator.

  Long-term operation of the motor in the opposite direction will damage the pump!

  Optional accessory overheat protection switch is provided. If the power supply of the pump is cut off beyond the specified temperature, the alarm signal can be triggered at the same time. The overheat protection switch can be installed on the screw plug position (6/26) of the fuel tank (6/27). No screw plug is installed. The 6.35mm FASTON clamp is used for electrical wiring.

  Power supply: 25VAC (maximum) 60VDC (maximum)

  3. Motor switch warning of vacuum oil filter

  If the safety switch or electrical failure will turn off the pump, the re-start of the pump can only be done manually.


日韩人妻系列在线观看| 婷婷91麻豆精品国产人妻| 午夜一区二区在线观看视频| 亚洲国产黄片在线播放| 精品日韩欧美精品日韩| 亚洲日本国产精品一区| 久热天堂在线视频精品伊人| 亚洲av香蕉一区区二区三区蜜 | 久久这里只有精品视频首页| 国产三级精品三级在专区中文| 国产精品久久三级三级| 午夜一区二区三区精品| 91亚洲精品综合久久水牛影 | 尤物蜜桃视频一区二区三区| 婷婷精品一区二区三区| 成人激情福利视频在线观看| 国产精品视频一区二区八戒| 国产精品粗又长一区| 日韩一二三四区免费观看| 国产一区在线免费在线观看| 久久免费网站91色网站| 精品国产美女诱惑久久久| 蜜臀精品一区二区av天堂| 麻豆精品情欲人妻二区| 国产日产精品久久一区| 精品国产一区二区三广区精东| 传媒视频在线观看完整版| 成人黄色小视频下载| 中文字幕一区二区三区久久久 | 日本人妻中文字幕一区| 日韩在线观看一二三四| 一级黄片一区二区三区| 国产极品丝袜福利在线| 日本免费人成黄页在线| 日韩av毛片在线观看| 国产精品三级玖玖玖电影| 国产精品流白浆在线观看| 亚洲区一区二区三区视频| 国产免费自拍激情视频| 精品无人乱码在哪里看| 国产精品国产三级国av麻豆|